Fire door commissioning requirements

Date:Oct 27, 2020

1. Normally closed fire doors, manually opened from either side of the door, should be closed automatically. When a signal feedback device is installed, the on and off status signals should be fed back to the fire control room.


2. The normally open fire escape door, after the fire detector on either side of the fire alarm, should automatically close, and the closing signal should be fed back to the fire control room.


3. The normally open emerg fire door should be automatically closed after receiving the closing instruction manually issued by the fire control room, and the closing signal should be fed back to the fire control room.


4. The normally open fireproof door should be automatically closed after receiving the closing instruction manually issued on site, and the closing signal should be fed back to the fire control room.